SECTION 330B UNIFORM AND CONCENTRATED LOADS

 
Category
Description
Uniform Load
Concentrated
Load
21 R-7 JLWQ,
R-8 Occupancy
Floors at grade or immediately above and below grade and other floors accessible by ramp or elevator. 60 2000
Floors other than described above including mezzanines. 50 0
Mezzanines, if posting of allowable live load is provided. 40 0
22 F-7 JLWQ,
F-8 Occupancy
Floors at grade or immediately above and below grade and other floors accessible by ramp or elevator. 75 2000
Floors other than described above including mezzanines. 60 0
Mezzanines, if posting of allowable live load is provided. 40 0
23 F-7 JLWQ,
R-7 JLWQ Occupancy
Sleeping Mezzanine 40 0
Built-In Sleeping Bunk 40 0
24 F-7 JLWQ
R-7 JLWQ Occupancy;
F-8 or R-8 Occupancy in existing buildings
Roof Exit Path For Alternative Emergency Escape and Rescue 40 0
Roof Exit Queuing Area (area= 3 sf per occupant served at the designated escape point offthe roof) 60 0